FEATURES
16 Digital Inputs and Outputs |
Compatible with TTL and CMOS |
Optic Isolated Inputs (6040-2) |
Form C Relay Outputs (6040-2) |
Programmable Glitch Capture |
Self Test Mode |
Input/Output Status Display |
DESCRIPTION
The 6040 provides 16 digital inputs and outputs for event recording and generation. The basic version,
6040-1, is compatible with TTL and CMOS logic levels. The 6040-2 has optic isolated inputs and form C
relay outputs. It also has a +12 VDC isolated power supply for use with control circuits that activate
the isolated optic inputs. The 6040 may be combined with other Series 6000 signal conditioning in turnkey
data acquisition and control systems.
State of the inputs is normally captured at the time of sampling. The alternate glitch capture mode gives
a true state if a 100 ns or wider pulse occured since the channel was last sampled. Inputs are monitored
for up to three alarm conditions. Board locations are provided for the installation of input filter components.
| Number |
16 |
| Sampling |
Programmable using the system sample rates. |
| Glitch Capture |
Program enabled to capture events of 100 nS or longer. |
| Alarms |
Continuous monitoring for specified bit patterns, consisting of high, low and masked bits, for warning, alarm and general alarm. |
| Connector |
50-pin Type D, Subminiature. |
| 6040-1 |
TTL/CMOS. Max input is 5.25 V. |
| 6040-2 |
Optic isolated, off is less than 1.45 V, on is greater than 3.7 V, input impedance is 360 Ohms. Input protected to ±50 Volts. Isolation is 450 Volts, input to input or input to system power ground. |
| Number |
50-socket Type D, Subminiature. |
| Connector |
16-bits, two's complement output. |
| 6040-1 |
CMOS. On is +4.8 Volts minimum; off is +0.15 Volts maximum from 1K Ohm source impedance. |
| 6040-2 |
One set of form C contacts, 2 A at 30 VDC. Maximum voltage is 220 VDC. |
| Output |
12 VDC, ±1%, 1.25 A maximum. |
| Isolation |
750 Volts, DC. |
|